SETPOINT CONFIGURATION DISPLAYS

MENU
/TARE
/NT/GRS
DESCRIPTION
SP 1
Setpoint 1
Scroll right one digit
Change the flashing digitÆs values.
Select from -1999 through 9999
SP 2
Setpoint 2
Scroll right one digit
Change the flashing digitÆs values.
Select from -1999 through 9999

SPECIFICATIONS

SIGNAL INPUT

Input Ranges
0-100 mV, ▒ 50 mV, 0-10 V, 0-5 V, 0-20 mA, 4-20 mA

Isolation to Earth Ground
Dielectric strength to 2500V transient per 3mm spacing based on EN 61010 for 260Vrms or dc working voltage

Noise Rejection

Normal Mode Rejection (NMR) = 60dB
Common Mode Rejection (CMR) = 120dB

Input Protection
Voltage Input = 120Vrms max
Current Input = 200mA max


Resistance

100 Meg ohms for 100 mV or ▒50 mV input range 1 Meg ohm for 10 V or +5 V input range 5 ohms for 20 mA current input range

Display
LED 14-segment, 13.8 mm (0.54")

Symbols: 8. 8. 8. 8.

ANALOG TO DIGITAL
Technique: Dual slope
Internal resolution: 15 bits
Read Rate: 3/sec Polarity Automatic

ACCURACY AT 25░C

Max Error Strain/Process:
▒0.03% of reading, ▒ 1 count

Span Tempco: 50 ppm/░C
Step Response: 1 sec
Warm Up to Rated Accuracy: 30 min

Excitation Voltage
AC power units
DC power units
24 V @ 25 mA
24 V @ 25 mA
12 V @ 50 mA
12 V @ 50 mA
10 V @ 120 mA
10 V @ 60 mA
5 V @ 60mA
5 V @ 60mA

Load Regulation: 1.1%
Line Regulation: 0.02% per Vac

ALARM OUTPUTS (if applicable)
2 Form "C" on/off relays. Configurable for latched and unlatched by software.
Max current: 5 AMPS, resistive load
Max voltage: 250 Vac or 30 Vdc

ANALOG OUTPUT (if applicable)
Signal Type: Current or voltage

Signal Level

  • Current: 10 V max compliance at 20 mA output
  • Voltage: 20 mA max for 0-10 V output


  • Function
    May be assigned to a display range or proportional control output with setpoint #1 when used as a control output.

    Linearity:
    0.2%

    Step Response Time
    2 - 3 seconds to 99% of the final value

    ISOLATED ANALOG OUTPUT (TB5, if applicable)
    Same as non-isolated analog output except isolated to 1000 Vdc.

    Signal Type: Current or voltage

    Signal Level
    Current: 10 V max compliance at 20 mA output
    Voltage: 20 mA max for 0-10 V output

    Function

    May be assigned to a display range or proportional control output with setpoint #1 when used as a control output.

    Linearity:
    0.2%

    Step Response Time
    2 - 3 seconds to 99% of the final value

    Only one analog output is available on each unit and it must be factory installed.

    INPUT POWER INFORMATION
    Voltage
  • AC - 115/230 Vrms ▒10%
  • DC - 9.5 at 950mA dc to 32 V dc at 250mA dc


  • Frequency: 50-60 Hz
    Power: 9.5 watts max.

    External Fuse Protection Recommended:
    AC
    115V
    IEC 127-2/III, 125mA, 250V (T Type) or UL Slow-Blow, 175mA, 250V
    AC
    230V
    IEC 127-2/III, 63mA, 250V (T Type) or UL Slow-Blow, 80mA, 250V

    ENVIRONMENT
    Operating Temperature: 0 to 50░C ((32░ to 122░F)
    Storage Temperature: -40░ to 85░C(-40░ to 185░ F)
    Relative Humidity: 90% at 40░C (non-condensing)

    MECHANICAL
    Panel cutout: 1/8 DIN 3.62" x 1.78" (45 x 92mm)
    Weight: 1.27 lb (575 g)

    Dimensions
    Dimensions
    Figure 8-1 Meter Dimensions