SETPOINT
CONFIGURATION DISPLAYS
MENU
|
/TARE
|
/NT/GRS
|
DESCRIPTION
|
SP
1
Setpoint 1
|
Scroll
right one digit
|
Change
the flashing digitÆs values.
|
Select from -1999 through 9999
|
SP
2
Setpoint 2
|
Scroll
right one digit
|
Change
the flashing digitÆs values.
|
Select
from -1999 through 9999
|
SPECIFICATIONS
SIGNAL
INPUT
Input Ranges
0-100 mV, ▒ 50 mV, 0-10 V, 0-5 V, 0-20 mA, 4-20 mA
Isolation to Earth Ground
Dielectric
strength to 2500V transient per 3mm spacing based on EN 61010 for 260Vrms
or dc working voltage
Noise Rejection
Normal Mode Rejection (NMR) = 60dB
Common Mode Rejection (CMR) = 120dB
Input Protection
Voltage Input = 120Vrms max
Current Input = 200mA max
Resistance
100 Meg ohms for 100 mV or ▒50 mV input range 1 Meg ohm for 10 V or +5
V input range 5 ohms for 20 mA current input range
Display
LED 14-segment, 13.8 mm (0.54")
Symbols: 8. 8. 8. 8.
ANALOG TO DIGITAL
Technique: Dual slope
Internal resolution: 15 bits
Read Rate: 3/sec Polarity Automatic
ACCURACY AT 25░C
Max Error Strain/Process:
▒0.03% of reading, ▒ 1 count
Span Tempco: 50 ppm/░C
Step Response: 1 sec
Warm Up to Rated Accuracy: 30 min
Excitation
Voltage
|
AC
power units
|
DC
power units
|
24
V @ 25 mA
|
24
V @ 25 mA
|
12
V @ 50 mA
|
12
V @ 50 mA
|
10
V @ 120 mA
|
10
V @ 60 mA
|
5
V @ 60mA
|
5
V @ 60mA
|
Load Regulation: 1.1%
Line Regulation: 0.02% per Vac
ALARM OUTPUTS (if applicable)
2
Form "C" on/off relays.
Configurable for latched
and unlatched by software.
Max current:
5 AMPS, resistive load
Max voltage:
250 Vac or 30 Vdc
ANALOG
OUTPUT (if applicable)
Signal Type: Current or voltage
Signal Level
Current: 10 V max compliance at 20 mA output
Voltage: 20 mA max for 0-10 V output
Function
May be assigned to a display range or proportional control output with
setpoint #1 when used as a control output.
Linearity: 0.2%
Step Response Time
2 - 3 seconds to 99% of the final value
ISOLATED ANALOG OUTPUT (TB5, if applicable)
Same as non-isolated analog output except isolated to 1000 Vdc.
Signal Type: Current or voltage
Signal Level
Current: 10 V max compliance at 20 mA output
Voltage: 20 mA max for 0-10 V output
Function
May be assigned to a display range or proportional control output with
setpoint #1 when used as a control output.
Linearity: 0.2%
Step Response Time
2 - 3 seconds to 99% of the final value
Only one analog output is available on each unit and it must be factory
installed.
INPUT
POWER INFORMATION
Voltage
AC - 115/230 Vrms ▒10%
DC - 9.5 at 950mA dc to 32 V dc at 250mA dc
Frequency: 50-60 Hz
Power: 9.5 watts max.
External Fuse Protection Recommended:
AC
|
115V
|
IEC 127-2/III, 125mA, 250V (T Type) or UL Slow-Blow, 175mA, 250V |
AC
|
230V
|
IEC
127-2/III, 63mA, 250V (T Type) or UL Slow-Blow, 80mA, 250V |
ENVIRONMENT
Operating Temperature: 0 to 50░C ((32░ to 122░F)
Storage Temperature: -40░ to 85░C(-40░ to 185░ F)
Relative Humidity: 90% at 40░C (non-condensing)
MECHANICAL
Panel cutout: 1/8 DIN 3.62" x 1.78" (45 x 92mm)
Weight: 1.27 lb (575 g)
|
Figure 8-1
Meter Dimensions
|
|